MIK-2200 Dual-loop digital display controller

Dual-loop digital display controller with automatic SMD packaging technology has a strong anti-jamming capability. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and to output alarm control, analog transmission, RS-485/232 communication etc.

Characteristics

Double four-digit LED display;

10 types of dimensions available;

Standard snap-in installation;

Power supply: AC/DC100~240V (Frequency 50/60Hz)  Power consumption≤5W DC 12~36V  Power consumption≤3W

  • Specification

 Product  Dual-loop digital display controller
 Model MIK-2200
 Display Dual-screen LED display
 Dimension A.160*80*110mm
B. 80*160*110mm
C. 96*96*110mm
D. 96*48*110mm
E. 48*96*110mm
F. 72*72*110mm
K. 160*80*110mm
L. 80*160*110mm
Measurement accuracy ±0.2%FS
Transmission output Analog output----Analog output----4-20mA、1-5v、
                             0-10mA、0-5V、0-20mA、0-10V
Alarm Output ALM---With upper and lower limit alarm function, with alarm return difference setting;Relay contact capacity:
AC125V/0.5A(small)DC24V/0.5A(small)(Resistance C load)
AC220V/2A(big)DC24V/2A(big)(Resistive load)
Note: When the load exceeds the relay contact capacity, please do not directly carry the load
Power supply AC/DC100~240V (Frequency50/60Hz) Power consumption≤5W
DC 12~36V  Power consumption≤3W
Use environment Operating temperature(-10~50℃)No condensation, no icing
Printout RS232 printing interface, micro-matched printer can realize manual, timing and alarm printing functions

 

  • Introduction

2200 Dual-loop digital controller

Dual-loop digital display controller

Dual-loop digital display controller with automatic SMD packaging technology has a strong anti-jamming capability. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and to output alarm control, analog transmission, RS-485/232 communication etc. Designed with dual-screen LED display, you can set the displaying contents of upper and lower screen, and through mathematic function you can make addition, subtraction, multiplication and division to the two input loop input signals, and it has a very good applicability.

Input signal type list:

Graduation Number Pn Signal type Measure range Graduation Number Pn Signal type Measure range
0 TC B 400~1800℃ 18 Remote Resistance 0~350Ω -1999~9999
1 TC S 0~1600℃ 19 Remote Resistance 3 0~350Ω -1999~9999
2 TC K 0~1300℃ 20 0~20mV -1999~9999
3 TC E 0~1000℃ 21 0~40mV -1999~9999
4 TC T -200.0~400.0℃ 22 0~100mV -1999~9999
5 TC J 0~1200℃ 23 -20~20mV -1999~9999
6 TC R 0~1600℃ 24 -100~100mV -1999~9999
7 TC N 0~1300℃ 25 0~20mA -1999~9999
8 F2 700~2000℃ 26 0~10mA -1999~9999
9 TC Wre3-25 0~2300℃ 27 4~20mA -1999~9999
10 TC Wre5-26 0~2300℃ 28 0~5V -1999~9999
11 RTD  Cu50 -50.0~150.0℃ 29 1~5V -1999~9999
12 RTD  Cu53 -50.0~150.0℃ 30 -5~5V -1999~9999
13 RTD  Cu100 -50.0~150.0℃ 31 0~10V -1999~9999
14 RTD  Pt100 -200.0~650.0℃ 32 0~10mA square -1999~9999
15 RTD  BA1 -200.0~600.0℃ 33 4~20mA square -1999~9999
16 RTD  BA2 -200.0~600.0℃ 34 0~5V square -1999~9999
17 Linear resistance 0~400Ω -1999~9999 35 1~5V square -1999~9999